Delta CFP2000 Series User Manual page 73

Ip55 fan and pump drive
Table of Contents

Advertisement

Chapter 5 Main Circuit TerminalsCFP2000
Frame D-1 / D-3
If you install at Ta 30°C environment, please select copper wire with voltage rating 600V and
temperature resistant at 75°C or 90°C.
If you install at Ta 30°C above environment, please select copper wire with voltage rating 600V and
temperature resistant at 90°C or above.
For UL installation compliant, please use copper wires for installation, the wire gauge is based on
temperature resistant at 75°C which is requested and recommended from UL. Do not reduce the
wire gauge when using higher temperature wire.
Model Name
VFD750FP4EA-41/52
VFD900FP4EA-41/52
Main Circuit Terminals:
R/L1, S/L2, T/L3, DC+, DC-, U/T1, V/T2,
W/T3
Max. Wire
Min. Wire Gauge
Gauge
3/0 AWG [95 mm
4/0 AWG
[120 mm
2
]
4/0 AWG [120 mm
Screw Spec.
Max. Wire
and Torque
Gauge
(±10%)
M8
2
]
4/0 AWG
200 kg-cm
[173.4 lb-in.]
[120 mm
2
]
[19.62 Nm]
5-14
Terminal:
Screw Spec.
Min. Wire Gauge
3/0 AWG [95 mm
2
]
[173.4 lb-in.]
2
]
4/0 AWG [120 mm
2
]
[19.62 Nm]
and Torque
(±10%)
M8
200 kg-cm