Delta CFP2000 Series User Manual page 240

Ip55 fan and pump drive
Table of Contents

Advertisement

Pr.
09-31
Internal communication protocol
09-33
PLC command force to 0
09-35
PLC address
09-36
CANopen slave address
09-37
CANopen speed
09-39
CANopen warning record
09-40
CANopen decoding method
09-41
CANopen communication status
09-42
CANopen control status
Parameter Name
Chapter 11 Summary of Parameter SettingsCFP2000
Setting Range
1: BACnet
0: Modbus 485
-1: Internal communication Slave 1
-2: Internal communication Slave 2
-3: Internal communication Slave 3
-4: Internal communication Slave 4
-5: Internal communication Slave 5
-6: Internal communication Slave 6
-7: Internal communication Slave 7
-8: Internal communication Slave 8
-10: Internal communication Master
-12: Internal PLC control
bit0: Before PLC scans, set up PLC target
frequency = 0
1–254
0: Disable
1–127
0: 1 Mbps
1: 500 Kbps
2: 250 Kbps
3: 125 Kbps
4: 100 Kbps (Delta only)
5: 50 Kbps
bit0: CANopen Guarding Time out
bit1: CANopen heartbeat Time out
bit2: CANopen SYNC Time out
bit3: CANopen SDO Time out
bit4: CANopen SDO buffer overflow
bit5: Can Bus off
bit6: Error protocol of CANopen
bit8: The setting values of CANopen indexes
are fail
bit9: The setting value of CANopen address
is fail
bit10: The checksum value of CANopen
indexes is fail
0: Disable (Delta-defined decoding method)
1: Enable (CANopen DS402 standard
protocol)
0: Node Reset
1: Com Reset
2: Boot up
3: Pre Operation
4: Operation
5: Stop
0: Not Ready for Use
1: Inhibit Start
2: Ready to Switch on
3: Switched on
11-31
Default
0
0000h
2
0
0
Read
only
1
Read
only
Read
only