Chapter 12 Description of Parameter SettingsCFP2000
Analog Input Selection (AVI1)
Analog Input Selection (ACI)
Analog Input Selection (AVI2)
Settings
Common applications for PID control
1.
Flow control: Use a flow sensor to feedback the flow data and perform accurate flow
control.
2.
Pressure control: Use a pressure sensor to feedback the pressure data and perform
precise pressure control.
3.
Air volume control: Use an air volume sensor to feedback the air volume data to achieve
excellent air volume regulation.
4.
Temperature control: Use a thermocouple or thermistor to feedback temperature data for
comfortable temperature control.
5.
Speed control: Use a speed sensor or encoder to feedback motor shaft speed or input
another machine speed as a target value for closed loop speed control of the master-slave
operation. Pr.10-00 sets the PID set point source (target value).
PID control loop:
Concept of PID control
 Proportional gain (P):
The output is proportional to input. With only proportional gain control, there is always a
steady-state error.
Adjustment: Turn off the Ti and Td, or remain Ti and Td in constant value, then adjust the
Increase: Faster status feedback, but excessive adjustment will increase the overshoot.
Decrease: Smaller overshoot, but excessive adjustment will slow down the transient
 Integral time(I):
The controller output is proportional to the integral of the controller input. To eliminate the
steady-state error, add an "integral part" to the controller. The integral time controls the
relation between integral part and the error. The integral part increases over time even if
4: PID target value
proportional gain (P).
response.
12.1-08-2
Default: 1
Default: 0
Default: 0