Delta CFP2000 Series User Manual page 262

Ip55 fan and pump drive
Table of Contents

Advertisement

 The keypad should be set to decimal when setting parameters.
Example: defined unit shows inWG and three decimal places.
In above data we could find inWG corresponds to 01Axh (x as the setting place of the decimal
place), and the three decimal places corresponds to 0003h, which displays 01A3h in
hexadecimal, and turns to decimal 01A3h=419. Set Pr.00-25=419 to complete the setting.
Maximum User-Defined Value
Settings
 When Pr.00-26 is NOT set to 0.
Pr.00-26 corresponds to Pr.01-00 (Maximum motor operating frequency).
Example: When the user-defined value is set as 100.0% corresponded to the maximum output
frequency 60.00 Hz, Pr.00-25 is set at 0021h, and Pr.00-26 is set as 100.0%.
NOTE
The drive display is controlled by the Pr.00-25 setting when Pr.00-25 is properly set and Pr.00-26
is not 0.
User-Defined Value
Settings
 Pr.00-27 displays the user-defined value when Pr.00-26 is not set to 0.
 The user-defined value is valid when Pr.00-20 (frequency source) is set to the digital keypad or to
RS-485 communication.
Switching from Auto mode to Hand mode
Settings
0: Disable
0–65535 (when Pr.00-25 set to no decimal place)
0.0–6553.5 (when Pr.00-25 set to 1 decimal place)
0.00–655.35 (when Pr.00-25 set to 2 decimal place)
0.000–65.535 (when Pr.00-25 set to 3 decimal place)
The user-defined value is enabled. The setting value of
Read only
bit0: Sleep function control bit
0: Sleep function control bit
1: Sleep function and Auto mode are the same
bit1: Control bit unit
0: Displaying unit in Hz
1: Same unit as the Auto mode
bit2: PID control bit
0: Cancel PID control
1: PID control and Auto mode are the same.
bit3: Frequency source control bit
0: Frequency source set up by parameter, if the multi-step speed is
activated, then multi-step speed has the priority.
1: Frequency command set up by Pr.00-30, regardless of whether the
multi-step speed is activated.
12.1-00-11
Chapter 12 Description of Parameter SettingsCFP2000
Default: 0
Default: Read only
Default: 0

Advertisement

Table of Contents
loading