9-2 Environment for Operation, Storage and Transportation
Do NOT expose the AC motor drive in the bad environment, such as dust, direct sunlight, corrosive/inflammable gasses,
humidity, liquid and vibration environment. The salt in the air must be less than 0.01mg/cm
Installation
location
Surrounding
Temperature
(°C)
Rated Humidity
Air Pressure
(kPa)
Pollution Level
Environment
Altitude
Vibration
Operating
Shock
Operating
Vibration
In protective
shipping
package
Shock
Operation
Maximum permanent angle in relation to the normal vertical
Position
mounting position
IEC60364-1/IEC60664-1 Pollution degree 2, Indoor use only
- 15– + 50 without derating,
Operation
+51–60 with derating
Storage
-25– +70
Transportation
-25– +70
Non-condensation, non-frozen
Operation
Max. 95%
Storage/
Max. 95%
Transportation
No condense water
Operation/
86–106
Storage
Transportation
70–106
IEC 60721-3-3
Operation
Class 3C3, Class 3S2
Storage
Class 1C2, Class 1S2
Transportation
Class 2C2, Class 2S2
If the AC motor drive is installed at an altitude 0–1000 m, follow normal
operation restriction. For every 100 m increase in altitude, the AC motor
drive needs to either lower rated current by 1% or by 0.5
temperature for operation.
Operation
If the drive is installed at an altitude above 2000 m, please refer to the
voltage derating graph in the user manual for more instructions.
Note: Voltage derating is not needed for a Center Ground System, and
maximum installation altitude is 4000m.
IEC 60068-2-6
Frame A: 2 Hz ≦ f ≦ 13.2 Hz / Amplitude 1 mm; 13.2 Hz < f ≦ 55 Hz / Gravity 0.7 G to 2.0 G;
55 Hz < f ≦ 512 Hz / Gravity 2.0 G
Frame B: 2 Hz ≦ f ≦ 13.2 Hz / Amplitude 1 mm; 13.2 Hz < f ≦ 55 Hz / Gravity 0.7 G to 1.5 G;
55 Hz < f ≦ 512 Hz / Gravity 1.5 G
Frame C / D0 / D:
2 Hz ≦ f ≦ 13.2 Hz / Amplitude 1 mm; 13.2 Hz < f ≦ 55 Hz / Gravity 0.7 G to 1.0 G;
55 Hz < f ≦ 512 Hz / Gravity 1.0 G
IEC 60068-2-27
Frame A; B; C; D0: Max 30 G; 11 ms
Frame D: Max 15 G; 11 ms
IEC 60068-2-64
10Hz ≦ f ≦ 100Hz / ASD: 1.0m2/s3
100Hz ≦ f ≦ 200Hz / Slope: -3dB/octave
Cardboard box type: Free fall drop in accordance with ISTA 1A
Wooden box type: In accordance with ISTA 1E (4 side incline) and ISTA 2B (Bottom side drop)
Chapter 9 Specifications CFP2000
9-5
2
every year.
10
10
o
C of