Chapter 12 Description of Parameter SettingsCFP2000
Frequency for Y-connection / ∆-connection Switch for an Induction Motor
Settings
Y-connection / ∆-connection Switch for Induction Motor
Settings
Delay Time for Y-connection / ∆-connection Switch for an Induction Motor
Settings
 You can apply Pr.05-23–Pr.05-25 in a wide range of motors, and the motor coil executes the
Y-connection / -connection switch as required. The wide range motors are related to the motor
design. In general, the motor has higher torque with low speed Y-connection, and has higher
speed with high speed -connection).
 Pr.05-24 enables and disables the switch of Y-connection / -connection.
 When you set Pr.05-24 as 1, the drive uses the Pr.05-23 setting and current motor frequency and
switches the current motor to Y-connection or -connection. You can switch the relevant motor
parameter settings simultaneously.
 Pr.05-25 sets the switch delay time of Y-connection / -connection.
 When the output frequency reaches Y-connection / -connection switch frequency, the drive
delays according to Pr.05-25 before activating the multi-function output terminals.
0.00–599.00 Hz
0: Disable
1: Enable
0.000–60.000 sec.
12.1-05-4
Default: 60.00
Default: 0
Default: 0.200