16-9 Explanation of various PLC speed mode controls
Speed mode supports SVC control. Under the speed mode of SVC control, it cannot be
performed successfully unless finish motor parameter auto tuning ahead of time.
Control methods and settings are explained as follows:
Speed control:
Register table for speed mode:
Control special M
Special M
M1025
Driver frequency = set frequency (ON)/driver frequency =0 (OFF)
M1026
Driver operating direction FWD(OFF)/REV(ON)
M1040
Hardware power (Servo On)
M1042
Quick stop
M1044
Pause (Halt)
M1052
Lock frequency (lock, frequency locked at the current operating frequency)
Status special M
Special M
M1015
Frequency attained (when used together with M1025)
M1056
Servo On Ready
M1058
On Quick Stopping
Control special D
Special D
D1060
Mode setting (speed mode is 0)
Status special D
Special D
D1037
Converter output frequency (0.00–600.00)
D1050
Actual operating mode (speed mode is 0)
Speed mode control commands:
FREQ (P)
Target speed
Example of speed mode control:
Before performing speed control, if the SVC control method is used, setting of electromechanical
parameters must first be completed.
1.
Setting D1060 = 0 will shift the converter to the speed mode (default).
2.
Use the FREQ command to control frequency, acceleration time, and deceleration time.
3.
Set M1040 = 1, the driver will now be excited, but the frequency will be 0.
4.
Set M1025 = 1, the driver frequency command will now jump to the frequency designated
by FREQ, and acceleration/deceleration will be controlled on the basis of the acceleration
time and deceleration time specified by FREQ.
5.
M1052 can be used to lock the current operating frequency.
6.
M1044 can be used to temporarily pause operation, and the deceleration method will comply
with deceleration settings.
Description of Function
Description of Function
Description of Function
Description of Function
S1
The first acceleration time setting
Chapter 16 PLC Function Applications│CFP2000
S2
The first deceleration time setting
16-143
Attributes
RW
RW
RW
RW
RW
RW
Attributes
RO
RO
RO
Attributes
RW
Attributes
RO
RO
S3