Delta CFP2000 Series User Manual page 441

Ip55 fan and pump drive
Table of Contents

Advertisement

Chapter 12 Description of Parameter SettingsCFP2000
Extension Card Output Terminal Selection (AO10)
Extension Card Output Terminal Selection (AO11)
Settings
 Refer to the function chart below for details setting.
Function Chart
Settings
Functions
0
Output frequency (Hz)
1
Frequency command (Hz) Maximum frequency Pr.01-00 is processed as 100%.
2
Motor speed (Hz)
3
Output current (rms)
4
Output voltage
5
DC bus voltage
6
Power factor
7
Power
9
AVI1
10
ACI
11
AVI2
20
CANopen analog output
21
RS-485 analog output
Communication card
22
analog output
23
Constant voltage output
0–23
Maximum frequency Pr.01-00 is processed as 100%.
Maximum frequency Pr.01-00 is processed as 100%.
(2.5 ᵡ rated current) is processed as 100%
(2 ᵡ rated voltage) is processed as 100%
450V (900V)=100%
-1.000–1.000=100%
(2 ᵡ rated power) is processed as 100%
0–10 V = 0–100%
4–20 mA = 0–100%
-10–10 V = 0–100%
For CANopen communication analog output
Terminal
AFM1
AFM2
AO10
AO11
For RS-485 (InnerCOM / Modbus) analog output
Terminal
AFM1
AFM2
AO10
AO11
For communication analog output (CMC-EIP01, CMC-PN01,
CMC-DN01)
Terminal
AFM1
AFM2
AO10
AO11
Pr.14-20 and Pr.14-21 control voltage output level
0–100% of Pr.14-20 corresponds to 0–10 V of AO10.
0–100% of Pr.14-21 corresponds to 0–10 V of AO11.
12.1-14-2
Default: 0
Descriptions
Corresponding
address
2026-A1
2026-A2
2026-AB
2026-AC
Corresponding
address
26A0H
26A1H
26AAH
26ABH
Corresponding
address
26A0H
26A1H
26AAH
26ABH