Delta CFP2000 Series User Manual page 318

Ip55 fan and pump drive
Table of Contents

Advertisement

Signal Loss Selection for Analog Input 4–20 mA
Settings
 Determines the response when the 4–20 mA signal is lost, when AVIc (Pr.03-28=2) or ACIc
(Pr.03-29=0).
 When Pr.03-28 is not set to 2, the voltage input to AVI1 terminal is 0–10 V or 0–20 mA, and the
Pr.03-19 is invalid.
 When Pr.03-29 is not set to 0, the voltage input to ACI terminal is 0–10 V, and the Pr.03-19 is
invalid.
 When the setting is 1 or 2, the keypad displays the warning code "ANL". It keeps blinking until the
ACI signal is recovered.
 When the setting is 3, and the ACI terminal is disconnected, the keypad displays "ACE" error. It
keeps blinking until the connection is recovered and the error is reset.
 When the motor drive stops, the warning condition does not continue to exist, so the warning
disappears.
Multi-function Output 1 (AFM1)
Multi-function Output 2 (AFM2)
Settings
Function Chart
Settings
0
Output frequency (Hz)
1
Frequency command (Hz)
2
Motor speed (Hz)
3
Output current (rms)
4
Output voltage
5
DC bus Voltage
6
Power factor
7
Power
9
AVI1 percentage
10
ACI percentage
11
AVI2 percentage
20
CANopen analog output
0: Disable
1: Continue operation at the last frequency
2: Decelerate to 0 Hz
3: Stop immediately and display ACE
0–23
Functions
12.1-03-17
Chapter 12 Description of Parameter SettingsCFP2000
Maximum frequency Pr.01-00 is regarded as 100%.
Maximum frequency Pr.01-00 is regarded as 100%.
Maximum frequency Pr.01-00 is regarded as 100%
(2.5 X rated current) is regarded as 100%
(2 X rated voltage) is regarded as 100%
450V (900V)=100%
-1.000–1.000=100%
Rated power is regarded as 100%
0–10 V / 0–20 mA / 4–20 mA =0–100%
4–20 mA / 0–10 V / 0–20 mA =0–100%
0–10 V = 0–100%
CANopen communication analog output
Terminal
AFM1
AFM2
AO10
AO11
Default: 0
Default: 0
Descriptions
Corresponding
address
2026-A1
2026-A2
2026-AB