 Setting 2: Frequency tracking starts from the minimum output frequency and accelerates to the
master Frequency command after the drive output frequency and motor rotator speed are
synchronous. Use this setting when there is little inertia and large resistance.
 This function is only valid when the RUN command is enabled.
Allowed Power Loss Duration
Settings
 Determines the maximum time of allowable power loss. If the duration of a power loss exceeds
this parameter setting, the AC motor drive stops output.
 Pr.07-06 is valid when the maximum allowable power loss time is ≤ 20 seconds and the AC
motor drive displays "Lv". If the AC motor drive is powered off due to overload, even if the
maximum allowable power loss time is ≤ 20 seconds, the operation mode set in Pr.07-06 does
not execute.
Base Block Time
Settings
 When momentary power loss is detected, the AC motor drive blocks its output and then waits for
a specified period of time (determined by Pr.07-08, called Base Block Time) before resuming
operation. Set this parameter to the time that allows the residual regeneration voltage at the
output side to decrease to 0V before activating the drive again.
 This parameter is not only for the B.B. time, but also is the re-start delay time after free run.
 The RUN command during a free run operation is memorized, and runs or stops with the last
frequency command after the delay time.
 This delay time is only applicable in "Re-start after coast to stop" status, and does not limit ramp
to stop. The coast to stop can be caused by various control command source, or by errors.
 Following table is the recommended setting for re-start delay time of each model power. You
must set Pr. 07-08 according to this table (the default of each model power is based on this table
as well).
kW
HP
Delay time (sec.)
kW
HP
Delay time (sec.)
0.0–20.0 sec.
0.0–5.0 sec. (Depending on the model power)
007
015
1
2
0.3
0.4
185
220
25
30
1.1
1.2
12.1-07-3
Chapter 12 Description of Parameter SettingsCFP2000
022
037
040
3
5
5.5
0.5
0.6
0.7
300
370
450
40
50
60
1.3
1.4
1.5
Default: 2.0
Default: Depending
on the model power
055
075
110
7.5
10
15
0.7
0.8
0.9
550
750
75
100
1.6
1.7
150
20
1
900
125
1.8