Delta CFP2000 Series User Manual page 162

Ip55 fan and pump drive
Table of Contents

Advertisement

8-10-5 Communication Parameters for CFP2000 Conneted to PROFINET
When operating CFP2000 via CMC-PN01, please set the control and operation command as
controlled by communication card. When CFP2000 is connected to PROFINET network, please
set up the communication parameters according to the table below.
Parameter
Pr.00-20
Pr.00-21
Pr.09-30
Pr.09-60
8-10-6 LED Indicator
LED
Ready out
MT out
SD
BF out
ACT PHY1
LINK PHY1
ACT PHY2
LINK PHY2
Set value (Dec)
8
The frequency command is controlled by communication card.
5
The operation command is controlled by communication card.
1
Set Pr.09-30 to 60xx or 20xx as the decoding method.
Identification: when CMC-PN01 is connected, Pr.09-60 will show
12
value 12.
Status
ON
Yellow
Flashes
OFF
Green
-
Red
-
ON
Red
Flashes
OFF
ON
Orange
Flashes
OFF
ON
Green
OFF
ON
Orange
Flashes
OFF
ON
Green
OFF
Chapter 8 Option Cards CFP2000
Explanation
PN Stack operates in normal status
PN Stack operates in normal status, and
waiting to sync with MCU
PN Stack operates with error
-
-
Connection with PROFINET Controller
breaks off
Connection is normal, but an error occurs
to the communication with PROFINET
Controller
Connection with PROFINET Controller is
normal
Online, exchanging data with the master
Off line, but handshaking data with the
master
Initial status
Network connection is normal
Network is not connected
On line, exchanging data with the master
Off line, but handshaking data with the
master
Initial status
Network connection is normal
Network is not connected
8-25