Chapter 16 PLC Function Applications│CFP2000
Example
LD
X0
RST
C0
LD
X1
CNT
C0 K5
LD
C0
OUT
Y0
1. When X0=On and the RST command is
executed, the current value of C0 will
revert to 0, and the output contact will
revert to Off.
2. When X1 changes from Off→On, the
current value of the counter will execute
an increase (add one).
3. When the count of counter C0 reaches the
set value K5, the contact C0 will come On,
and the current value of C0= set value
=K5. Afterwards, signal C0 triggered by X1
cannot be received, and the current value
of C0 will remain K5.
X0
RST C0
X1
CNT
C0
K5
C0
Y0
16-30