Delta CFP2000 Series User Manual page 82

Ip55 fan and pump drive
Table of Contents

Advertisement

6-2 Specifications of Control Terminal
Terminal
Group
function
Relay
Control
board
Control
board
Wiring precautions:
In the figure above, the default for STO1, STO2, +24V and SCM1, SCM2, DCM are short circuit.
The +24V from section
purposes. The default for +24V-COM is short circuit and SINK mode (NPN); please refer to
Section 4 Wiring for more detail.
Tighten the wiring with slotted screwdriver:
is 3.5 mm (wide) x 0.6 mm (thick);
Ⓐ Ⓑ
When wiring bare wires, make sure they are perfectly arranged to go through the wiring holes.
Terminals
Digital control signal common
+24V
(Source)
COM
Digital control signal common (Sink)
FWD
Forward-Stop command
REV
Reverse-Stop command
Conductor
length [mm]
Solid
Strand
Solid
Strand
Solid
Strand
of above figure is for STO only, and cannot be used for other
Terminal Function
Figure 6-18
Stripping
Max. wire
gauge
4–5
1.5 mm
2
[16 AWG]
6–7
is 2.5 mm (wide) x 0.4 mm (thick)
Factory Setting (NPN mode)
+24V  5% 200 mA
Common for multi-function input terminals
FWD-DCM:
ON forward running
OFF deceleration to stop
REV-DCM:
ON reverse running
OFF deceleration to stop
6-7
Chapter 6 Control TerminalsCFP2000
Min. wire
Torque (±10%)
gauge
5 kg-cm
[4.3 lb-in]
[0.49 Nm]
8 kg-cm
0.2 mm
2
[6.9 lb-in]
[26 AWG]
[0.78 Nm]
2 kg-cm
[1.7 lb-in]
[0.20 Nm]
Table 6-1