Chapter 12 Description of Parameter SettingsCFP2000
(drive's rated current) x Pr.06-71 (low current setting level)% = low current detection level (A).
The drive changes the setting for Pr.00-01 (rated current) according to the setting for Pr.00-16
(load selection).
dEb Motion Offset
Settings
Fire Mode
Settings
This parameter works with multi-input function terminal 58 or 59 and multi-output function
terminal 53 and 54.
0: Fire mode is disabled.
1: When there is a fire, the motor operates in counter clockwise direction (U, V, W).
2: When there is a fire, the motor operates in clockwise direction (U, W, V).
Operating Frequency when Running Fire Mode
Settings
Sets the drive's frequency when the fire mode is enabled.
Enable Bypass on Fire Mode
Settings
Bypass Delay Time on Fire Mode
Settings
Number of Times of Reset in Fire Mode
Settings
Length of Time of Reset in Fire Mode
Settings
The settings for Pr.06-82 to Pr.06-85 determine whether to switch motors to operate under
mains electricity when in fire mode.
0.0–200.0 V
DC
0: Disable
1: Operates in counter clockwise direction
2: Operates in clockwise direction
0.00–599.00 Hz
0: Disable Bypass
1: Enable Bypass
0.0–6550.0 sec.
0–10
0.0–6000.0 sec.
12.1-06-25
Default: 40.0
Default: 0.00
Default: 60.00
Default: 0
Default: 0.0
Default: 0
Default: 60.0