Delta CFP2000 Series User Manual page 168

Ip55 fan and pump drive
Table of Contents

Advertisement

460V Models
Frame Size
Model VFD_ _ _ FP4EA- _ _ _
Rated output capacity [kVA]
Rated output current [A]
Applicable motor output [kW]
Applicable motor output [HP]
Overload tolerance
Max. output frequency [Hz]
Carrier frequency [kHz]
Rated output capacity [kVA]
Rated output current [A]
Applicable motor output [kW]
Applicable motor output [HP]
Overload tolerance
Max. output frequency [Hz]
Carrier frequency [kHz]
Input current [A] Light duty
Input current [A] Normal duty
Rated voltage / Frequency
Operating voltage range
Frequency tolerance
Efficiency [%]
Power factor
Weight [kg]
Cooling method
Braking chopper
DC choke
EMC Filter
NOTE
The carrier frequency is default. Increasing the carrier frequency requires a reduction in current. Please refer to Section 9-4
Derating Curve for Ambient Temperature.
Select the AC motor drive with capacity one grade oarger for the impact load application.
C
300
370
48
58
60
73
30
37
40
50
120% of rated current can endure for 1 minute during every 5 minutes
36
48
45
60
22
30
30
40
120% of rated current can endure for 1 minute during every 5 minutes
160% of rated current can endure for 3 seconds during every 30 seconds.
60
73
45
60
3-phase 380–480 V
26.5
Built-in DC reactor EN61000-3-12
Built-in EMC Filter EN61800-3 C1 & C2
9-3
Chapter 9 Specifications CFP2000
D0
450
550
73
88
91
110
45
55
60
75
599 Hz
2–10 (6 kHz)
58
73
73
91
37
45
50
60
599 Hz
2–10 (6 kHz)
91
110
73
91
(-15%–10%), 50/60 Hz
AC
323–528 V
AC
47–63 Hz
97
>0.98
42
Fan cooling
Frame A to C (built-in)
D
750
900
120
143
150
180
75
90
100
125
2–9
(4 kHz)
88
120
110
150
55
75
75
100
2–9
(4 kHz)
150
180
110
150
59.5