You can set the frequency command (F) within the range of skip frequencies. Then the output
frequency (H) is limited to the lower limit of skip frequency ranges.
When accelerating and decelerating, the output frequency still passes the skip frequency ranges.
Zero-speed Mode
Settings
When the frequency command of drive is less than Fmin (Pr.01-07 or Pr.01-41), the drive
operates according to the setting value.
0: the AC motor drive is in waiting mode without voltage output from terminals U, V, W.
1: the drive executes the DC brake by Vmin (Pr.01-08 and Pr.01-42) in V/F and SVC modes.
2: the AC motor drive runs using Fmin (Pr.01-07, Pr.01-41) and Vmin (Pr.01-08, Pr.01-42) in V/F
and SVC modes.
In V/F and SVC modes
V/F Curve Selection
Settings
0: Waiting for output
1: Zero-speed operation
2: Minimum frequency (Refer to Pr.01-07, Pr.01-41)
0: V/F curve determined by Pr.01-00–01-08
1: 1.5
V/F curve
th
2: 2
V/F curve
nd
3: 60 Hz, voltage saturation in 50 Hz
4: 72 Hz, voltage saturation in 60 Hz
5: 50 Hz, decrease gradually with cube
6: 50 Hz, decrease gradually with square
7: 60 Hz, decrease gradually with cube
12.1-01-9
Chapter 12 Description of Parameter SettingsCFP2000
Default: 0
Default: 0