Chapter 16 PLC Function Applications│CFP2000
API
FREQ
142
Bit device
X
Y
M
S1
S2
S3
Notes on operand usage: none
S2, S3: In acceleration/deceleration time settings, the number of decimal places is
determined by the definitions of Pr.01-45.
Example
When Pr.01-45=0: units of 0.01 sec.
The setting of 50 for S2 (acceleration time) in the ladder diagram below implies 0.5 sec,
and the S3 (deceleration time) setting of 60 implies 0.6 sec
The FREQ command can control driver frequency commands, and acceleration and
deceleration time; it also uses special register control actions, such as:
M1025: Control driver RUN(On)/STOP(Off) (RUN requires Servo On (M1040 On) to be
effective)
M1026: Control driver operating direction FWD(Off)/REV(On)
M1040: Control Servo On/Servo Off.
M1042: Trigger quick stop (ON)/does not trigger quick stop (Off).
M1044: Pause (On)/release pause (Off)
M1052: Lock frequency (On)/release lock frequency (Off)
M1025: Driver RUN (On) / STOP (Off), M1026: driver operating direction FWD (Off) / REV
(On). M1015: frequency reached.
When M10=On, sets the driver frequency command K300 (3.00 Hz), with an
acceleration/deceleration time of 0.
When M11=Off, the drive frequency command will now change to 0
Pr.09-33 are defined on the basis of whether the reference commands have been cleared
before PLC operation.
bit0: Prior to PLC scanning procedures, whether the target frequency has been cleared is
0. (This will be written to the FREQ command when the PLC is ON).
S1
S2
S3
P
Word device
K
H
KnX KnY KnM
S1
: Frequency command.
When M11=On, sets the driver frequency command K3000 (30.00 Hz), with an
acceleration time of 50 (0.5 sec.) and deceleration time of 60 (0.6 sec.). (When
Pr.01-45=0)
M1000
M11
M1000
M12
M13
M14
M10
M11
M11
M10
Driver speed control mode
16-bit command (7 STEP)
FREQ
T
C
D
32-bit command
Flag signal: M1015
S2
: Acceleration time.
M1025
M1026
M1040
M1042
M1044
M1052
FREQP
K300
K0
K3000
K50
FREQ
END
16-124
Continuous
FREQP
execution type
execution type
S3
: Deceleration time
K0
K60
Pulse