Chapter 12 Description of Parameter SettingsCFP2000
Settings
9
Drive is ready
Low voltage warning
10
(Lv)
11
Malfunction indication
Mechanical Brake
12
Release (Pr.02-32)
13
Over-heat warning
Software brake signal
14
indication
15
PID feedback error
16
Slip Error (oSL)
Count value reached,
17
does not return to 0
(Pr.02-20)
Counter value reached,
18
returns to 0 (Pr.02-19)
External interrupt B.B.
19
input (Base Block)
20
Warning Output
21
Over-voltage
Over-current stall
22
prevention
Over-voltage stall
23
prevention
Operation mode
24
indication
25
Forward command
26
Reverse command
Output when Current ≥
27
Pr.02-33
Output when Current <
28
Pr.02-33
Output when frequency
29
≥ Pr.02-34
Output when Frequency
30
< Pr.02-34
Y-connection for the
31
motor coil
∆-connection for the
32
motor coil
Zero Speed (actual
33
output frequency)
Zero Speed includes
34
stop (actual output
frequency)
Error output selection 1
35
(Pr.06-23)
Error output selection 2
36
(Pr.06-24)
Functions
Active when the drive is ON with no error detected.
Active when the DC bus voltage is too low (refer to Pr.06-00 low
voltage level).
Active when fault occurs (except Lv stop).
Active when the drive runs after the set delayed time for Pr.02-32.
This function must use with DC brake function.
Active when IGBT or heat sink overheats, to prevent the drive from
shutting down due to over-heating (refer to Pr.06-15).
Active when the soft brake function is ON (refer to Pr.07-00).
Active when the PID feedback signal error is detected.
Active when the slip error is detected.
When the drive executes external counter, this contact is active if the
count value is equal to the setting value for Pr.02-20. This contact is
not active when the setting value for Pr.02-20 > Pr.02-19.
When the drive executes the external counter, this contact is active if
the count value is equal to the setting value for Pr.02-19.
Active when external interrupt (B.B.) stop output occurs in the drive.
Active when a warning is detected.
Active when the over-voltage is detected.
Active when the over-current stall prevention is detected.
Active when the over-voltage stall prevention is detected.
Active when the operation command is NOT controlled by digital
keypad. (Pr.00-21≠0)
Active when the operation direction is forward.
Active when the operation direction is reverse.
Active when the current is ≥ Pr.02-33.
Active when the current is < Pr.02-33
Active when the frequency is ≥ Pr.02-34.
Active when the frequency is < Pr.02-34.
Active when Pr.05-24=1, the frequency output is lower than Pr.05-23
minus 2Hz, and the time is longer than Pr.05-25.
Active when Pr.05-24=1, the frequency output is higher than Pr.05-23
plus 2Hz, and the time is longer than Pr.05-25.
Active when the actual output frequency is 0. (the drive is in RUN
mode)
Active when the actual output frequency is 0 or Stopped.
Active when Pr.06-23 is ON.
Active when Pr.06-24 is ON.
12.1-02-12
Descriptions