Delta CFP2000 Series User Manual page 343

Ip55 fan and pump drive
Table of Contents

Advertisement

Chapter 12 Description of Parameter SettingsCFP2000
 Sets the acceleration / deceleration time selection when stall prevention occurs at constant
speed.
Over-torque Detection Selection (OT1)
Settings
Over-torque Detection Selection (OT2)
Settings
 When you set Pr.06-06 and Pr.06-09 to 1 or 3, a warning message displays, but there is not error
record.
 When you set Pr.06-06 and Pr.06-09 to 2 or 4, a warning message displays and there is an error
record.
Over-torque Detection Level (OT1)
Settings
Over-torque Detection Level (OT1)
Settings
Over-torque Detection Level (OT2)
Settings
Over-torque Detection Time (OT2)
Settings
 When the output current exceeds the over-torque detection level (Pr.06-07 or Pr.06-10) and
exceeds the over-torque detection time (Pr.06-08 or Pr.06-11), the over-torque detection follows
the setting of Pr.06-06 and Pr.06-09.
4: By the 4
acceleration / deceleration time
th
5: By automatic acceleration / deceleration
0: No function
1: Continue operation after over-torque detection during constant speed
operation
2: Stop after over-torque detection during constant speed operation
3: Continue operation after over-torque detection during RUN
4: Stop after over-torque detection during RUN
0: No function
1: Continue operation after over-torque detection during constant speed
operation
2: Stop after over-torque detection during constant speed operation
3: Continue operation after over-torque detection during RUN
4: Stop after over-torque detection during RUN
10–200% (100% corresponds to the light-load rated current of the drive)
0.0–60.0 sec.
10–200% (100% corresponds to the light-load rated current of the drive)
0.0–60.0 sec.
12.1-06-7
Default: 0
Default: 0
Default: 120
Default: 0.1
Default: 120
Default: 0.1