Chapter 12 Description of Parameter SettingsCFP2000
Settings
Functions
68
Disable Motor 8
69
Preheating Command
UP/DOWN Key Mode
Settings
Constant speed, Acceleration or Deceleration Speed of the UP/DOWN Key
Settings
Use when the multi-function input terminals are set to 19, 20 (UP / DOWN command). The
frequency increases or decreases according to Pr.02-09 and Pr.02-10.
When Pr.02-09 is set to 0: the increasing or decreasing frequency command (F) operates
according to the setting for acceleration or deceleration time (refer to Pr.01-12–Pr.01-19)
When Pr.02-09 is set to 1: the increasing / decreasing frequency command (F) operates
according to the setting for Pr.02-10 (0.01–1.00 Hz/ms).
Multi-function Input Response Time
Settings
Sets the response time of the digital input terminals FWD, REV and MI1–MI8.
This function is to delay and confirm the digital input terminal signal. The time for delay is also the
ON: if the preheating function is open and drive is in STOP status,
the preheating function is executed; until the contact status
changes to OFF, or the drive status turns to RUN and stops the
preheating function. Refer to Pr.02-72–02-73 for detail.
0: Up / Down by the acceleration or deceleration time
1: Up / Down constant speed (Pr.02-10)
0.001–1.000 Hz/ms
0.000–30.000 sec.
12.1-02-8
Descriptions
Default: 0
Default: 0.001
Default: 0.005