Delta CFP2000 Series User Manual page 508

Ip55 fan and pump drive
Table of Contents

Advertisement

ID*
Display on LCD Keypad
17
Action level
Action time
Fault treatment parameter
Reset method
Reset condition
Record
Cause
Check if the ambient temperature
or temperature inside the control
cabinet is too high, or if there is
obstruction in the ventilation hole
of the control cabinet.
Check if there is any obstruction on
the heat sink or if the fan is
running.
Insufficient ventilation space
Check if the drive matches the
corresponding load
The drive has run 100% or more
than 100% of the rated output for a
long time
Unstable power
Load changes frequently
oH1/ oH2 warning level
Model
VFD007FP4EA-41/52/52S
VFD015FP4EA-41/52/52S
VFD022FP4EA-41/52/52S
VFD037FP4EA-41/52/52S
VFD040FP4EA-41/52/52S
VFD055FP4EA-41/52/52S
VFD075FP4EA-41/52/52S
VFD110FP4EA-41/52/52S
VFD150FP4EA-41/52/52S
VFD185FP4EA-41/52/52S
VFD220FP4EA-41/52/52S
VFD300FP4EA-41/52/52S
VFD370FP4EA-41/52/52S
VFD450FP4EA-41/52/52S
VFD550FP4EA-41/52/52S
VFD750FP4EA-41/52/52S
VFD900FP4EA-41/52/52S
Fault Name
Heatsink overheating
Capacitance temperature exceeds the protection level
(oH2)
Action and Reset
Refer to the table below for oH2 level of each models
When capacitance temperature exceeds the protection level for more than 100
ms, oH2 error occurs
N/A
Manual reset
Reset when c
apacitance temperature is lower than oH2 error level minus (-) 10°C
Yes
1. Check ambient temperature.
2. Regularly inspect the ventilation hole of the control cabinet.
3. Change the installed place if there are heating objects, such as braking
resistors, in the surroundings.
4. Install/ add cooling fan or air conditioner to lower the temperature inside the
cabinet.
Remove the obstruction or replace the cooling fan.
Increase ventilation space of the drive.
1. Reduce the load
2. Reduce the carrier
3. Replace the drive with a larger capacity model.
Replace the drive with a larger capacity model.
Install reactor(s)
Reduce load changes
oH1
oH2
110
85
100
105
90
110
97
100
90
95
85
14-13
Chapter 14 Fault Codes and DescriptionsCFP2000
Fault Descriptions
Corrective Actions
oH warning
oH1 warning = (Pr.06-15)
oH1 Warning = Pr.06-15
oH2 Warning = oH2 – 5
Unit: °C