Delta CFP2000 Series User Manual page 224

Ip55 fan and pump drive
Table of Contents

Advertisement

Pr.
Parameter Name
03-21
Analog output gain 1 (AFM1)
Analog output 1 in REV direction
03-22
(AFM1)
03-24
Analog output gain 2 (AFM2)
Analog output 2 in REV direction
03-25
(AFM2)
03-27
AFM2 output bias
03-28
AVI1 terminal input selection
03-29
ACI terminal input selection
PLC analog output terminal
03-30
status
03-31
AFM2 output selection
03-32
AFM1 DC output setting level
03-33
AFM2 DC output setting level
03-34
AFM1 output selection
03-35
AFM1 filter output time
03-36
AFM2 filter output time
Multi-function MO output by AI
03-44
level source
03-45
AI upper level
03-46
AI lower level
03-50
Analog input curve selection
Chapter 11 Summary of Parameter SettingsCFP2000
Setting Range
6: Power factor
7: Power
9: AVI1%
10: ACI%
11: AVI2%
20: CANopen analog output
21: RS-485 analog output
22: Communication card analog output
23: Constant voltage output
0.0–500.0%
0: Absolute value of output voltage
1: Reverse output 0 V; forward output 0–10 V
2: Reverse output 5–0 V; forward output 5–10 V
0.0–500.0%
0: Absolute value of output voltage
1: Reverse output 0 V; forward output 0–10 V
2: Reverse output 5–0 V; forward output 5–10 V
-100.00–100.00%
0: 0–10 V
1: 0–20 mA
2: 4–20 mA
0: 4–20 mA
1: 0–10 V
2: 0–20 mA
Monitor the status of PLC analog output terminals
0: 0–20 mA output
1: 4–20 mA output
0.00–100.00%
0: 0–20 mA output
1: 4–20 mA output
0.00–20.00 sec.
0: AVI1
1: ACI
2: AVI2
-100.00–100.00%
-100.00–100.00%
0: Regular curve
1: Three-point curve of AVI1
2: Three-point curve of ACI
3: Three-point curve of AVI1 & ACI
4: Three-point curve of AVI2
5: Three-point curve of AVI1 & AVI2
6: Three-point curve of ACI & AVI2
7: Three-point curve of AVI1 & ACI & AVI2
11-15
Default
100.0
0
100.0
0
0.00
0
0
Read
only
0
0.00
0
0.01
0
50.00
10.00
7