Delta CFP2000 Series User Manual page 241

Ip55 fan and pump drive
Table of Contents

Advertisement

Chapter 11 Summary of Parameter SettingsCFP2000
Pr.
09-45
CANopen master function
09-46
CANopen master address
09-50
BACnet MS / TP node address
09-51
BACnet baud rate
09-52
BACnet Device index L
09-53
BACnet Device index H
09-55
BACnet Max Address
09-56
BACnet password
09-60
Communication card identifications
09-61
Firmware version of communication card
09-62
Product code
09-63
Fault code
Communication card address
09-70
(for DeviceNet or PROFIBUS)
Communication card speed setting
09-71
(for DeviceNet)
Additional settings for communication
09-72
card speed (for DeviceNet)
Parameter Name
Setting Range
4: Enable Operation
7: Quick Stop Active
13: Error Reaction Active
14: Error
0: Disable
1: Enable
0–127
0–127
9.6–76.8 Kbps
0–65535
0–63
0–127
0–65535
0: No communication card
1: DeviceNet slave
2: Profibus-DP slave
3: CANopen slave / master
4: Modbus–TCP Slave
5: EtherNet/IP Slave
8: BACnet IP
12: PROFINET
Read only
Read only
Read only
DeviceNet: 0–63
Profibus-DP: 1–125
Standard DeviceNet:
0: 125 Kbps
1: 250 Kbps
2: 500 Kbps
3: 1 Mbps (Delta only)
Non-standard DeviceNet: (Delta only)
0: 10 Kbps
1: 20 Kbps
2: 50 Kbps
3: 100 Kbps
4: 125 Kbps
5: 250 Kbps
6: 500 Kbps
7: 800 Kbps
8: 1 Mbps
0: Standard DeviceNet
In this mode, baud rate can only be 125
Kbps, 250 Kbps, 500 Kbps in standard
DeviceNet speed
11-32
Default
0
100
10
38.4
10
0
127
0
Read
only
Read
only
Read
only
Read
only
1
2
0