Delta CFP2000 Series User Manual page 291

Ip55 fan and pump drive
Table of Contents

Advertisement

Chapter 12 Description of Parameter SettingsCFP2000
Settings
Analog output control
51
for RS-485 interface
Output control for
52
communication cards
53
Fire mode indication
Bypass fire mode
54
indication
55
Motor 1 output
56
Motor 2 output
57
Motor 3 output
58
Motor 4 output
59
Motor 5 output
60
Motor 6 output
61
Motor 7 output
62
Motor 8 output
66
SO output logic A (N.O.)
68
SO output logic B (N.C.)
Analog input level
67
reached
Functions
For RS-485 interface (InnerCOM / Modbus) communication control
output.
Physical
terminal
RY1
RY2
MO1
MO2
MO10/RA10
MO11/RA11
RY12
RY13
RY14
RY15
Control the output through communication cards (CMC-EIP01,
CMC-PN01 and CMC-DN01)
Physical
terminal
RY1
RY2
RY3
MO10/RY10
MO11/RY11
RY12
RY13
RY14
RY15
This function is enabled when setting 58 or 59 is enabled.
The contact works when bypass function is enabled in the fire mode.
When setting multi-motor circulative function, the multi-function output
terminal automatically sets up Pr.02-13–Pr.02-15 and Pr.02-36–
Pr.02-40 in accordance with the setting for Pr.12-01.
Status of drive
STL1–STL3
The multi-function output terminals operate when the analog input
level is between the high level and the low level.
Pr.03-44: Select one of the analog signal channels (AVI1, ACI, and
Pr.03-45: The high level for the analog input, default is 50.00%
Pr.03-46: The low level for the analog input, default is 10.00%.
If analog input > Pr.03-45, the multi-function output terminal operates.
If analog input < Pr.03-46, the multi-function output terminal stops
output.
12.1-02-14
Descriptions
Setting of related
parameters
Pr.02-13 = 51
Pr.02-14 = 51
Pr.02-16 = 51
Pr.02-17 = 51
Pr.02-36 = 51
Pr.02-37 = 51
Pr.02-38 = 51
Pr.02-39 = 51
Pr.02-40 = 51
Pr.02-41 = 51
Setting of related
parameters
Pr.02-13 = 52
Pr.02-14 = 52
Pr.02-15 = 52
Pr.02-36 = 52
Pr.02-37 = 52
Pr.02-38 = 52
Pr.02-39 = 52
Pr.02-40 = 52
Pr.02-41 = 52
N.O. (MOx=66)
Normal
Broken circuit (Open)
STO
Short circuit (Close)
Short circuit (Close)
AVI2) to be compared.
Attribute
Corresponding Index
RW
The bit0 at 2640h
RW
The bit1 at 2640h
RW
The bit3 at 2640h
RW
The bit 4 at 2640h
RW
The bit5 at 2640h
RW
The bit6 at 2640h
RW
The bit7 at 2640h
RW
The bit8 at 2640h
RW
The bit9 at 2640h
RW
The bit10 at 2640h
Attribute
Corresponding Index
RW
The bit0 at 2640
RW
The bit1 at 2640
RW
The bit2 at 2640
RW
The bit5 at 2640
RW
The bit6 at 2640
RW
The bit7 at 2640
RW
The bit8 at 2640
RW
The bit9 at 2640
RW
The bit10 at 2640
Status of safety output
N.C. (MOx=68)
Short circuit (Close)
Broken circuit (Open)
Broken circuit (Open)