Delta CFP2000 Series User Manual page 560

Ip55 fan and pump drive
Table of Contents

Advertisement

Index Sub
Definition
0 Number
1 Error code
2 AC motor drive status
2021H
Freq. command
3
(XXX.XX Hz)
4 Output freq. (XXX.XX Hz)
5 Output current (XX.X A)
6 DC bus voltage (XXX.X V)
7 Output voltage (XXX.X V)
The current segment run by
8
the multi-segment speed
command
9 Reserved
A Display counter value (c)
Display output power angle
B
(XX.X°)
Display output torque
C
(XXX.X%)
Display actual motor speed
D
(rpm)
10 Power output (X.XXX kWh)
Multi-function display
17
(Pr.00-04)
0 Reserved
1 Display output current
2 Display counter value
2022H
Display actual output
3
frequency (XXX.XX Hz)
Display DC bus voltage
4
(XXX.X V)
Factory
R/W
Size
Setting
10
R
U8
High byte: Warn code
0
R
U16
Low byte: Error code
0
R
U16
0
R
U16
0
R
U16
0
R
U16
0
R
U16
0
R
U16
0
R
U16
0
R
U16
0
R
U16
0
R
U16
0
R
U16
0
R
U16
0
R
U16
0
R
U16
0
R
U16
0
R
U16
0
R
U16
0
R
U16
0
R
U16
15-15
Chapter 15 CANopen Overview│CFP2000
Note
:
bit1
1
Reset
bit2
1: Base Block (B.B) ON
bit15–3 Reserved
:
00B
stop
:
01B
decelerate to stop
:
bit1–0
10B
waiting for operation
command
:
11B
in operation
:
bit2
1
JOG command
:
00B
run forward
:
01B
switch from run in reverse
to run forward
bit4–3
:
10B
switch from run forward to
run in reverse
:
11B
run in reverse
bit7–5
Reserved
:
1
master frequency command
bit8
controlled by communication
interface
:
1
master frequency command
bit9
controlled by analog signal
input
:
1
operation command
bit10
controlled by communication
interface
bit11
1: Parameter lock
1: Enable the digital keypad
bit12
copy parameter function
bit15–13 Reserved

Advertisement

Table of Contents
loading

Table of Contents