Chapter 12 Description of Parameter SettingsCFP2000
However, if the decreasing demands for flow quantity and pressure are too big, the
CFP2000 stops the current operating motors and waits for the delay time setting for Pr.12-04. It
continues doing this until the last motor stops using mains electricity. See sequential diagram
12-5 and 12-6 below.
Diagram 12-5: Sequence of Fixed Quantity Circulation with PID – Decreasing Demands
12.1-12-6