Delta CFP2000 Series User Manual page 359

Ip55 fan and pump drive
Table of Contents

Advertisement

Chapter 12 Description of Parameter SettingsCFP2000
Set up process:
1.
Switch AFM2 to 0
diagram)
2.
Wiring (Refer to Figure 1, PT100 wiring diagram):
Connect external terminal AFM2 to (+)
Connect external terminal ACM to (-)
Connect external terminals AFM2 and AVI1 to "short-circuit"
3.
Set Pr.03-00=11 or Pr.03-23=23 or Pr.03-33=45% (9 mA).
4.
Refer to the RTD temperature and resistance comparison table
Temperature=135°C, resistance=151.71 ; input current: 9 mA, voltage: about 1.37 V
Temperature=150°C, resistance=157.33 ; input current: 9 mA, voltage: about 1.42 V
5.
When the RTD temperature is > 135°C, the drive decelerates to the specified operation
frequency automatically. Then, Pr.06-56=1.37 and Pr.06-58=10 Hz. When Pr.06-58=0, it
disables the specified operation frequency.
6.
When the RTD temperature is > 150°C, the drive outputs a fault, decelerates to STOP, and
displays the warning 'oH3'. Then, Pr.06-57=1.42 and Pr.06-29=1 (fault and ramp to stop).
Software Detection GFF Current Level
Settings
Software Detection GFF Filter Time
Settings
 When the drive detects that the unbalanced three-phase output current is higher than the setting
for Pr.06-60, GFF protection activates. The drive then stops output.
Operation Time of Fault Record 1 (Day)
Operation Time of Fault Record 2 (Day)
Operation Time of Fault Record 3 (Day)
Operation Time of Fault Record 4 (Day)
Settings
Operation Time for Fault Record 1 (Min)
Operation Time for Fault Record 2 (Min)
Operation Time for Fault Record 3 (Min)
Operation Time for Fault Record 4 (Min)
Settings
 If there is any malfunctions when the drive operates, Pr.06-17–Pr.16-22 record the malfunctions,
and Pr.06-63–Pr.06-70 record the operation time for four sequential malfunctions. Check if there
is any problem with the drive according to the interval of the recorded fault.
20 mA on the I/O control terminal block. (Refer to Figure 1, PT100 wiring
0.0–6553.5% (100% corresponds to the light-load rated current of the drive)
0.00–655.35 sec.
0–65535 days
0–1439 min
12.1-06-23
DC
DC
Default: 60.0
Default: 0.10
Default: Read only
Default: Read only