Delta CFP2000 Series User Manual page 292

Ip55 fan and pump drive
Table of Contents

Advertisement

Settings
Preheating output
69
indication
FAN warning detection
70
output
 Remote IO function is added to directly make the drive control its AO/DO and read current AI/DI
status through the standard Modbus. The corresponding index of 26xx is as follows.
bit15
bit14
2600h
MI15
MI14
2640h
-
-
2660h
AVI1
2661h
ACI
2662h
AVI2
266Ah
AI10
266Bh
AI11
26A0h
AFM1
26A1h
AFM2
26AAh
AO10
26ABh
AO11
In addition, the AI and DI values can be read directly, and DO and AO have to be controlled by
Modbus for corresponding parameter functions. The tables below shown the related parameter
definition.
DO
Terminal
RY1
RY2
RY3
MO10 / RY10
MO11 / RY11
MO12
MO13
MO14
MO15
AO
Terminal
AFM1
AFM2
AFM10
AFM11
Multi-function Output Direction
Settings 0000h–FFFFh (0: N.O.; 1: N.C.)
 This parameter is in hexadecimal.
 This parameter is set by a bit. If the bit is 1, the corresponding multi-function output acts in an
opposite way.
Example: Assume Pr.02-13=1 (indication when the drive is operating). If the output is positive, the
bit is set to 0, and then Relay is ON when the drive runs and is OFF when the drive stops. On the
contrary, if the output is negative, and the bit is set to 1, then the Relay is OFF when the drive
runs and is ON when the drive stops.
bit15 bit14 bit13 bit12 bit11 bit10
MO20 MO19 MO18 MO17 MO16 MO15 MO14 MO13 MO12 MO11 MO10 Reserved
Functions
Active when the preheating is detected.
The terminal works when the internal fan warning activates.
bit13
bit12
bit11
bit10
MI13
MI12
MI11
MI10
-
-
-
MO15
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Pr. Setting
Pr.02-13 = 51
Pr.02-14 = 51
Pr.02-15 = 51
Pr.02-36 = 51
Pr.02-37 = 51
Pr.02-38 = 51
Pr.02-39 = 51
Pr.02-40 = 51
Pr.02-41 = 51
Pr. Setting
Pr.03-20 = 21
Pr.03-23 = 21
Pr.14-12 = 21
Pr.14-13 = 21
bit9
Chapter 12 Description of Parameter SettingsCFP2000
Descriptions
bit6
bit9
bit8
bit7
MI8
MI7
MI6
MI5
MO14 MO13
MO12
MO11
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Direct control the index corresponded to Modbus
bit0 of 2640h
bit1 of 2640h
bit2 of 2640h
bit5 of 2640h
bit6 of 2640h
bit7 of 2640h
bit8 of 2640h
bit9 of 2640h
bit10 of 2640h
Direct control the index corresponded to Modbus
The value of 26A0h
The value of 26A1h
The value of 26AAh
The value of 26ABh
bit8
bit7
bit6
12.1-02-15
bit5
bit4
bit3
bit2
MI4
MI3
MI2
MI1
-
-
RY3
MO10
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Default: 0000h
bit5
bit4
bit3
bit2
RY3
bit1
bit0
REV
FWD
RY2
RY1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
bit1
bit0
RY2
RY1