Chapter 7 Optional Accessories CFP2000

7-2 Magnetic Contactor / Air Circuit Breaker and Non-fuse Circuit Breaker

Magnetic Contactor (MC) and Air Circuit Breaker (ACB)
It is recommended the surrounding temperature for MC should be ≥ 60°C and that for ACB should be
≥ 50°C. In the meanwhile, consider temperature derating for components with ON/OFF switch in
accordance with the ambient temperature of the on-site distribution panel.
Frame
VFD007FP4EA-41/-52/-52S
VFD015FP4EA-41/-52/-52S
VFD022FP4EA-41/-52/-52S
A
VFD037FP4EA-41/-52/-52S
VFD040FP4EA-41/-52/-52S
VFD055FP4EA-41/-52/-52S
VFD075FP4EA-41/-52/-52S
VFD110FP4EA-41/-52/-52S
B
VFD150FP4EA-41/-52/-52S
VFD185FP4EA-41/-52/-52S
VFD220FP4EA-41/-52/-52S
C
VFD300FP4EA-41/-52/-52S
VFD370FP4EA-41/-52/-52S
VFD450FP4EA-41/-52/-52S
D0
VFD550FP4EA-41/-52/-52S
VFD750FP4EA-41/-52/-52S
D
VFD900FP4EA-41/-52/-52S
Light duty output
Model
Light duty input
current [A]
current [A]
3
4.2
5.5
8.5
10.5
13
18
24
32
38
45
60
73
91
110
150
180
7-8
MC/ACB selection
[A]
3
7
4.2
7
5.5
9
8.5
18
10.5
18
13
22
18
32
24
40
32
50
38
65
45
75
60
105
73
130
91
150
110
185
150
265
180
330
Table 7-4