Chapter 16 PLC Function Applications│CFP2000
PLC mode
Using KPC-CC01
Disable
PLC Run
PLC Stop
Maintain previous
NOTE
When input/output terminals (FWD REV MI1–MI8, MI10–15, Relay1–3, RY10–RY15,
MO10–MO11,) are included in the PLC program, these input / output terminals will only be
used by the PLC. As an example, when the PLC program controls Y0 during PLC operation
(PLC1 or PLC2), the corresponding output terminal relay (RA / RB / RC) will operate in
accordance with the program. At this time, the multifunctional input/output terminal setting
will be ineffective. Because these terminal functions are already being used by the PLC, the
DI / DO / AO in use by the PLC can be determined by looking at Pr.02-52, Pr.02-53, and
Pr.03-30.
When the PLC's procedures use special register D1040, the corresponding AO contact
AFM1 will be occupied, and AFM2 corresponding to special register D1045 will have the
same situation.
Pr.03-30 monitors the state of action of the PLC function analog output terminal; bit0
corresponds to the AFM1 action state, and bit1 corresponds to the AFM2 action state.
PLC Mode select bit1(52)
state
OFF
OFF
ON
ON
16-6
PLC Mode select bit0 (51)
OFF
ON
OFF
ON