Delta CFP2000 Series User Manual page 353

Ip55 fan and pump drive
Table of Contents

Advertisement

Chapter 12 Description of Parameter SettingsCFP2000
Detection Time of Output Phase Loss
Settings
Current Detection Level of Output Phase Loss
Settings
DC Brake Time of Output Phase Loss
Settings
 Setting Pr.06-48 to 0 disables the OPHL detection function.
 Status 1: The drive is in operation
When any phase current is less than the Pr.06-47 setting, and exceeds Pr.06-46 setting time,
the drive acts according to the Pr.06-45 setting.
 Status 2: The drive is in STOP; Pr.06-48=0 ; Pr.07-02≠0
After the drive starts, the DC brake operates according to Pr.07-01 and Pr.07-02. During this
period, OPHL detection is not active. After the DC brake action is completed, the drive starts to
run, and enables the OPHL protection as mentioned above for status 1.
0.000–65.535 sec.
0.00–100.00%
0.000–65.535 sec.
12.1-06-17
Default: 0.500
Default: 1.00
Default: 0.000

Advertisement

Table of Contents
loading

Table of Contents