Minimum mounting clearance
Frame
A–B
C–D
NOTE
The minimum mounting clearances A–D stated in the table above applies to AC motor drives installation. Failing to
follow the minimum mounting clearances may cause the fan to malfunction and heat dissipation problems.
VFD007FP4EA-41, VFD007FP4EA-52, VFD007FP4EA-52S,
VFD015FP4EA-41, VFD015FP4EA-52, VFD015FP4EA-52S,
VFD022FP4EA-41,VFD022FP4EA-52, VFD022FP4EA-52S,
Frame A
VFD037FP4EA-41,VFD037FP4EA-52, VFD037FP4EA-52S,
VFD040FP4EA-41,VFD040FP4EA-52, VFD040FP4EA-52S,
VFD055FP4EA-41,VFD055FP4EA-52, VFD055FP4EA-52S,
VFD075FP4EA-41, VFD075FP4EA-52, VFD075FP4EA-52S
VFD110FP4EA-41,VFD110FP4EA-52, VFD110FP4EA-52S,
VFD150FP4EA-41,VFD150FP4EA-52, VFD150FP4EA-52S,
Frame B
VFD185FP4EA-41,VFD185FP4EA-52, VFD185FP4EA-52S,
VFD220FP4EA-41, VFD220FP4EA-52, VFD220FP4EA-52S
VFD300FP4EA-41, VFD300FP4EA-52, VFD300FP4EA-52S,
Frame C
VFD370FP4EA-41,VFD370FP4EA-52, VFD370FP4EA-52S
VFD450FP4EA-41,VFD450FP4EA-52, VFD450FP4EA-52S,
Frame D0
VFD550FP4EA-41,VFD550FP4EA-52, VFD550FP4EA-52S
VFD750FP4EA-41,VFD750FP4EA-52, VFD750FP4EA-52S,
Frame D
VFD900FP4EA-41,VFD900FP4EA-52, VFD900FP4EA-52S
Figure 2-4
A [mm]
B [mm]
60
100
NOTE
The mounting clearance stated in the figure is for installing the drive in an
open area. To install the drive in a confined space (such as cabinet or
electric box), please follow the following rules: (1) Keep the minimum
mounting clearances. (2) Install a ventilation equipment or an air
conditioner to keep surrounding temperature lower than operation
temperature. (3) Refer to parameter setting and set up Pr.00-16, Pr.00-17
and Pr.06-55.
The table below shows the heat dissipation and the required air volume
when installing a single drive in a confined space. When installing multiple
drives, the required air volume shall be multiplied by the number the
drives.
Refer to the table below (Airflow Rate for Cooling) for ventilation
equipment design and selection.
Refer to the table below (Power Dissipation for AC Motor Drive) for air
conditioner design and selection.
Different control mode affects the derating. See Pr.06-55 for more
information.
Refer to Section 9-4 for ambient temperature derating curve and derating
curves under different control mode.
C [mm]
15
25
2-3
Chapter 2 InstallationCFP2000
D [mm]
-
-
-
-
Table 2-1
Table 2-2