09 Communication Parameters
COM1 Communication Address
Settings
 If RS-485 serial communication controls the AC motor drive, you must set the communication
address for this drive in this parameter. Each AC motor drive's communication address must be
different.
COM1 Transmission Speed
Settings
 Sets the transmission speed of the computer and the drive.
 Options are 4.8 Kbps, 9.6 Kbps, 19.2 Kbps, 38.4 Kbps, 57.6 Kbps and 115.2 Kbps; otherwise,
the transmission speed is set to the default 9.5 Kbps.
COM1 Transmission Fault Treatment
Settings
 Set the response for Modbus communication errors with the host. Set the detection time in
Pr.09-03.
COM1 Time-out Detection
Settings
 Sets the communication transmission time-out.
COM1 Communication Protocol
Settings
When us ing communication devi ces,
connects AC dr ive with P C by us ing
Delta IFD6530 or IFD6500.
1–254
4.8–115.2 Kbps
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning, no fault and continue operation
0.0–100.0 sec.
1: 7, N, 2 (ASCII)
2: 7, E, 1 (ASCII)
3: 7, O, 1 (ASCII)
4: 7, E, 2 (ASCII)
5: 7, O, 2 (ASCII)
6: 8, N, 1 (ASCII)
Chapter 12 Description of Parameter SettingsCFP2000
 The parameter can be set during the operation.
8
1
Modbus RS- 485
Pin 1~2,7,8: Reserv ed
Pin 3, 6: GND
Pin 4: SG-
Pin 5: SG+
RS-485
12.1-09-1
Default: 1
Default: 9.6
Default: 3
Default: 0.0
Default: 1