Delta CFP2000 Series User Manual page 700

Ip55 fan and pump drive
Table of Contents

Advertisement

API
CANTX
264
P
Bit device
X
Y
M
K
S1
S2
S3
S4
Notes on operand usage: none
S1
S4
The CANTX command can write a value to the index of the corresponding slave
station. When it is executed, it will send the SDO message format to the slave
station. M1066 and M1067 will both be 0 at that time, and M1066 will be set as 1
after reading. If the slave station gives the correct response, it will write the value
to the preset register, and set M1067 as 1. If the slave station has a response
error, M1067 will be set as 0, and an error message will be recorded to D1076 to
D1079.
API
CANFLS
265
P
Bit device
X
Y
M
K
D
Notes on operand usage: none
D
The CANFLS command can refresh special D commands. When is a read only
attribute, executing this command will send a message equivalent to that of CANRX
to the slave station, and the number of the slave station will be transmitted back and
refreshed to this special D. When there is a read/write attribute, executing this
command will send a message equivalent to that of CANTX to the slave station, and
the value of this special D will be written to the corresponding slave station.
When M1066 and M1067 are both 0, and M1066 is set as 1 after reading, if the slave
station gives a correct response, the value will be written to the designated register,
and M1067 will be set as 1. If the slave station's response contains an error, then
M1067 will be set as 0, and an error message will be recorded to D1076-D1079.
API
ICOMR
320
D
P
Bit device
X
Y
M
K
S1
S2
S3
D
Notes on operand usage: none
S1
: Selection of slave device.
S3
PLC).
The ICOMR command can obtain the slave station's converter and the internal
PLC's register value.
S1
S2
S3
S4
Word device
H
KnX KnY KnM
T
: Slave station number.
: Subindex+bit length.
D
Word device
H
KnX KnY KnM
T
: Special D to be refreshed.
D
Word device
H
KnX KnY KnM
T
D
: Read address.
Chapter 16 PLC Function Applications│CFP2000
Write CANopen slave station data
16-bit command (9 STEP)
CANTX
Continuous
C
D
execution type
32-bit command
Flag signal
S2
: Address to be written.
Refresh special D corresponding to CANopen
16-bit command (3 STEP)
CANFLS
Continuous
C
D
execution type
32-bit command
Flag signal
Internal communications read
16-bit command (9 STEP)
ICOMR
Continuous
C
D
execution type
32-bit command (17 STEP)
DICOMR Continuous
execution type
Flag signal: M1077 M1078 M1079
S2
: Device selection (0: converter, 1: internal
: Saving target.
16-127
CANTXP
Pulse
execution type
S3
: Main index.
CANFLSP
Pulse
execution type
ICOMRP
Pulse
execution type
DICOMRP
Pulse
execution
type