Chapter 12 Description of Parameter SettingsCFP2000
Master Frequency Command (AUTO) Source / Source Selection of the PID Target
Settings
Set the master frequency source in AUTO mode.
Pr.00-20 and Pr.00-21 are for settings the frequency source and operation source in AUTO mode.
Pr.00-30 and Pr.00-31 are for settings the frequency source and operation source in HAND mode.
You can switch the AUTO/HAND mode with the keypad KPC-CC01 or the multi-function input
terminal (MI).
The default for the frequency source or operation source is AUTO mode. It returns to AUTO mode
whenever you cycle the power. If you use a multi-function input terminal to switch between AUTO
and HAND mode, the highest priority is the multi-function input terminal. When the external
terminal is OFF, the drive does not accept any operation signal and cannot execute JOG.
Operation Command (AUTO) Source
Settings
Determines the operation command source in AUTO mode.
When you control the operation command by the keypad KPC-CC01, keys RUN, STOP and JOG
(F1) are valid.
Stop Method
Settings
Determines how the motor is stopped when the drive receives the Stop command.
0: Digital keypad
1: RS-485 communication
2: External analog input (Pr.03-00–Pr.03-02)
3: External UP/DOWN terminal (multi-function input terminal)
6: CANopen communication card
8: Communication card (does not include CANopen card)
0: Digital keypad
1: External terminals
2: RS-485 communication
3: CANopen communication card
5: Communication card (does not include CANopen card)
0: Ramp to stop
1: Coast to stop
12.1-00-8
Default: 0
Default: 0
Default: 0