Chapter 12 Description of Parameter SettingsCFP2000
Master Frequency Command (AUTO) Source / Source Selection of the PID Target
Settings
 Set the master frequency source in AUTO mode.
 Pr.00-20 and Pr.00-21 are for settings the frequency source and operation source in AUTO mode.
Pr.00-30 and Pr.00-31 are for settings the frequency source and operation source in HAND mode.
You can switch the AUTO/HAND mode with the keypad KPC-CC01 or the multi-function input
terminal (MI).
 The default for the frequency source or operation source is AUTO mode. It returns to AUTO mode
whenever you cycle the power. If you use a multi-function input terminal to switch between AUTO
and HAND mode, the highest priority is the multi-function input terminal. When the external
terminal is OFF, the drive does not accept any operation signal and cannot execute JOG.
Operation Command (AUTO) Source
Settings
 Determines the operation command source in AUTO mode.
 When you control the operation command by the keypad KPC-CC01, keys RUN, STOP and JOG
(F1) are valid.
Stop Method
Settings
 Determines how the motor is stopped when the drive receives the Stop command.
0: Digital keypad
1: RS-485 communication
2: External analog input (Pr.03-00–Pr.03-02)
3: External UP/DOWN terminal (multi-function input terminal)
6: CANopen communication card
8: Communication card (does not include CANopen card)
0: Digital keypad
1: External terminals
2: RS-485 communication
3: CANopen communication card
5: Communication card (does not include CANopen card)
0: Ramp to stop
1: Coast to stop
12.1-00-8
Default: 0
Default: 0
Default: 0