2.3 Commandable Binary Value Object
In CFP2000, we have BV_000
BV_Objects, we also can use (Multi) Read_Service to access Priority_Array and Relinquish_Default
properties.
Object
R/W
Number
BV 000
RW
BV 001
RW
BV 002
RW
BV 003
RW
BV 004
RW
BV 005
RW
BV 006
RW
BV 007
RW
BV 008
RW
BV 009
RW
BV 010
RW
BV 011
RW
BV 012
RW
BV 013
RW
BV 014
RW
BV 015
RW
2.4 Status (Readonly) Binary Value Object
In CFP2000, we have BV_016
we do NOT have Priority_Array and Relinquish_Default properties.
Object
R/W
Number
BV 016
BV 017
BV 018
BV 019
BV 020
BV 021
BV 022
BV 023
BV 024
BV 025
BV 026
BV 027
BV_015 supporting commandable Present_Value property. For these
Object Name
ACTIVE CMD
FWD/REV CMD
Reserved
HALT CMD
LOCK CMD
Reserved
QSTOP CMD
ServoPower CMD
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
RESET
BV_031 with readonly Present_Value property. For these BV_Objects,
Object Name
R
ARRIVE STATE
R
FWD/REV STATE
R
WARN STATE
R
ERROR STATE
R
Reserved
R
Reserved
R
QSTOP STATE
R
ServoPower STATE
R
Reserved
R
Reserved
R
Reserved
R
Reserved
Chapter 17 Introduction to BACnet │CFP2000
Object Description
(0)FreqCmd=0;(1)FreqCmd=FreqRefValue
(0)Forward; (1)Reverse
Reserved
(0)None;(1)RampDown to 0 Hz.
(0)None;(1)OutputFreq stays at current frequency
Reserved
(0)None;(1)Force driver quick stop
(0)PowerOff(free run to stop);(1)PowerOn
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
RESET:(0)Do nothing;(1)Reset fault
Object Description
(0)Not yet;(1)Arrive (OutputFreq=FreqCmd)
(0)Forward;(1)Reverse
(0)No Warn;(1)Occur Warn
(0)No Error;(1)Occur Error
Reserved
Reserved
(0)No QSTOP;(1)Occur QSTOP
(0)PowerOff(free run to stop);(1)PowerOn
Reserved
Reserved
Reserved
Reserved
17-5