Delta CFP2000 Series User Manual page 282

Ip55 fan and pump drive
Table of Contents

Advertisement

Settings
Functions
B.B. input from external
11
(B.B.: Base Block)
Output Stop
12
(Output pause)
Cancel the setting for
13
auto-acceleration /
auto-deceleration time
Switch between motor 1
14
and motor 2
Rotating speed
15
command from AVI1
Rotating speed
16
command from ACI
Rotating speed
17
command from AVI2
18
Forced to stop (Pr.07-20) ON: the drive ramps to stop according to Pr.07-20 setting.
19
Digital Up command
20
Digital Down command
PID function disabled
21
22
Clear the counter
Chapter 12 Description of Parameter SettingsCFP2000
ON: the output of the drive stops immediately. The motor is in free
run and the keypad displays the B.B. signal. Refer to Pr.07-08 for
details.
When the switch is ON, output of the drive stops immediately and
the motor is in free run status. The drive is in output waiting status
until the switch is turned to OFF, and then the drive restarts and
runs to the current setting frequency.
Set Pr.01-44 to one of the Pr.01-04 setting modes before using this
function. When this function is enabled, OFF is for auto mode and
ON is for linear acceleration / deceleration.
ON: use parameters for motor 2 .
OFF: use parameters for motor 1.
ON: force the source of the frequency to be AVI1. (If the rotating
speed commands are set to AVI1, ACI and AVI2 at the same time,
the priority is AVI1>ACI>AVI2)
ON: force the source of the frequency to be ACI. (If the rotating
speed commands are set to AVI1, ACI and AVI2 at the same time.
The priority is AVI1>ACI>AVI2)
ON: force the source of the frequency to be AVI2. (If the rotating
speed commands are set to AVI1, ACI and AVI2 at the same time.
The priority is AVI1>ACI>AVI2)
ON: the frequency of the drive increases or decreases by one unit.
If this function remains ON continuously, the frequency increases
or decreases according to Pr.02-09 / Pr.02-10.
The Frequency command returns to zero when the drive stops, and
the displayed frequency is 0.0 Hz. If you select Pr.11-00, bit7 = 1,
the frequency is not saved.
ON: the PID function is disabled.
ON: the current counter value is cleared and displays "0". The drive
counts up when this function is disabled.
12.1-02-5
Descriptions