 Ramp to stop: the AC motor drive decelerates to 0 or the minimum output frequency according
to the set deceleration time, and then to stop (according to Pr.01-07).
 Coast to stop: the AC motor drive stops output immediately, and the motor coasts to stop
according to the load inertia.
(1) Use "ramp to stop" for the safety of personnel, or to prevent material from being wasted in
applications where the motor must stop immediately after the drive stops. You must set the
deceleration time accordingly.
(2) If idling is allowed, or the load inertia is large, use "coast to stop". For example, blowers,
punching machines and pumps
Motor Direction Control
Settings
 Enables the AC motor drives to run in the forward and reverse direction. You can use it to prevent
a motor from running in a direction that would cause injure or damage to the equipment.
Digital Operator (Keypad) Frequency Command Memory
Settings
 If keypad is the frequency command source, when Lv or Fault occurs, this parameter stores the
current frequency command.
User-Defined Characteristics
Settings
0: Enable forward / reverse
1: Disable reverse
2: Disable forward
Read only
bit0–3: user-defined decimal place
0000b: no decimal place
0001b: one decimal place
0010b: two decimal place
0011b: three decimal place
bit4–15: user-defined unit
000xh: Hz
001xh: rpm
002xh: %
003xh: kg
004xh: m/s
005xh: kW
006xh: HP
007xh: ppm
008xh: 1/m
009xh: kg/s
00Axh: kg/m
12.1-00-9
Chapter 12 Description of Parameter SettingsCFP2000
Default: 0
Default: Read only
Default: 0