Delta CFP2000 Series User Manual page 746

Ip55 fan and pump drive
Table of Contents

Advertisement

Status (Readonly) Binary Value Object
In VFD-CFP2000, we have BV_016–BV_031 with readonly Present_Value property. In these
BV_Objects, we do NOT have Priority_Array and Relinquish_Default properties.
Object
R/W
Number
BV 016
R
BV 017
R
BV 018
R
BV 019
R
BV 020
R
BV 021
R
BV 022
R
BV 023
R
BV 024
R
BV 025
R
BV 026
R
BV 027
R
BV 028
R
BV 029
R
BV 030
R
BV 031
R
Object Name
BV_016_ARRIVE STATE
BV_017_FWD/REV STATE
BV_018_WARN STATE
BV_019_ERROR STATE
BV_020_Reserved
BV_021_Reserved
BV_022_QSTOP STATE
BV_023_ServoPower STATE
BV_024_Reserved
BV_025_Reserved
BV_026_Reserved
BV_027_Reserved
BV_028_Reserved
BV_029_Reserved
BV_030_Reserved
BV_031_Reserved
Chapter 17 Introduction to BACnet │CFP2000
(0)Not yet;(1)Arrive (OutputFreq=FreqCmd)
(0)Forward;(1)Reverse
(0)No Warn;(1)Occur Warn
(0)No Error;(1)Occur Error
Reserved
Reserved
(0)No QSTOP;(1)Occur QSTOP
(0)PowerOff(free run to stop);(1)PowerOn
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
17-15