Chapter 12 Description of Parameter SettingsCFP2000
04 Multi-Step Speed Parameters
1
Step Speed Frequency
st
2
Step Speed Frequency
nd
3
Step Speed Frequency
rd
4
Step Speed Frequency
th
5
Step Speed Frequency
th
6
Step Speed Frequency
th
7
Step Speed Frequency
th
8
Step Speed Frequency
th
9
Step Speed Frequency
th
10
Step Speed Frequency
th
11
Step Speed Frequency
th
12
Step Speed Frequency
th
13
Step Speed Frequency
th
14
Step Speed Frequency
th
15
Step Speed Frequency
th
Settings
 Use the multi-function input terminals (refer to setting 1–4 of Pr.02-01–Pr.02-08 and
Pr.02-26–Pr.02-31 Multi-function Input Command) to select the multi-step speed command (the
maximum is 15
in the following diagram.
 The external terminal/digital keypad/communication controls the RUN and STOP commands with
Pr.00-21.
 You can set each multi-step speed between 0.00–599.00 Hz during operation.
 Explanation for the timing diagram of the multi-step speed and external terminals.
The related parameter settings are:
1. Pr.04-00–04-14: sets the 1
2. Pr.02-01–02-08 and Pr.02-26–02-31: sets the multi-function input terminals (multi-step speed
command 1–4)
Related parameters:
Pr.01-22 JOG Frequency
Pr.02-01 Multi-function Input Command 1 (MI1)
Pr.02-02 Multi-function Input Command 2 (MI2)
Pr.02-03 Multi-function Input Command 3 (MI3)
Pr.02-04 Multi-function Input Command 4 (MI4)
0.00–599.00 Hz
step speed). Pr.04-00 to Pr.04-14 set the multi-step speed frequency as shown
th
to 15
st
th
 This parameter can be set during operation.
multi-step speed (to set the frequency of each step speed)
12.1-04-1
Default: 0.00