Delta CFP2000 Series User Manual page 222

Ip55 fan and pump drive
Table of Contents

Advertisement

Pr.
Parameter Name
The width of the desired frequency
02-25
reached 2
02-32
Brake delay time
Output current level setting for
02-33
multi-function output terminal
Output frequency setting for
02-34
multi-function output terminal
External operation control selection
02-35
after reset and activate
Display the status of multi-function
02-50
input terminal
Display the status of multi-function
02-51
output terminal
Display the external multi-function
02-52
input terminals used by PLC
Display the external multi-function
02-53
output terminals used by PLC
Display the frequency command
02-54
executed by external terminal
02-70
IO card types
 02-72
Preheating output current level
 02-73
Preheating output cycle
Chapter 11 Summary of Parameter SettingsCFP2000
Setting Range
0.00–599.00 Hz
0.000–65.000 sec.
0–150%
0.00–599.00 Hz
0: Disable
1: Drive runs if the RUN command remains after
reset or reboot
Monitor the status of multi-function input terminals
Monitor the status of multi-function output
terminals
Monitor the status of PLC input terminals
Monitor the status of PLC output terminals
0.00–599.00 Hz (Read only)
1: EMC-BPS01
4: EMC-D611A
5: EMC-D42A
6: EMC-R6AA
11: EMC-A22A
0–100%
0–100%
11-13
Default
2.00
0.000
0
3.00
0
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only
0
0