Frame D-2
If you install at Ta 30°C environment, please select copper wire with voltage rating 600 V and
temperature resistant at 75°C or 90°C.
If you install at Ta 30°C above environment, please select copper wire with voltage rating 600 V and
temperature resistant at 90°C or above.
For UL installation compliant, please use copper wires for installation, the wire gauge is based on
temperature resistant at 75°C which is requested and recommended from UL. Do not reduce the
wire gauge when using higher temperature wire.
Model Name
Max. Wire
VFD750FP4EA-52S
4/0 AWG
[120 mm
VFD900FP4EA-52S
Main Circuit Terminals:
R/L1, S/L2, T/L3 (Stranded wire only)
Min. Wire Gauge
Gauge
3/0 AWG [95 mm
]
2
4/0 AWG [120 mm
Chapter 5 Main Circuit TerminalsCFP2000
Terminal: DC+, DC-, U/T1, V/T2, W/T3,
Screw Spec.
Max. Wire
and Torque
Gauge
(±10%)
M8
2
]
4/0 AWG
200 kg-cm
[173.4 lb-in.]
[120 mm
2
]
[19.62 Nm]
5-15
Screw Spec.
Min. Wire Gauge
and Torque
3/0 AWG [95 mm
2
]
200 kg-cm
[173.4 lb-in.]
]
2
4/0 AWG [120 mm
2
]
[19.62 Nm]