Chapter 12 Description of Parameter SettingsCFP2000
Terminal Counting Value Reached (return to 0)
Settings
 You can set the input point for the counter using the multi-function terminal MI6 as a trigger
terminal (set Pr.02-06 to 23). When counting is completed, the specified multi-function output
terminal is activated (Pr.02-13, Pr.02-14, Pr.02-36, Pr.02-37 are set to 18), and Pr.02-19 cannot
be set to 0 at this time.
Example: When the displayed value is c5555, the drive count is 5,555 times. If the displayed
value is c5555, the actual count value is 55,550–55,559.
Preliminary Counting Value Reached (does not return to 0)
Settings
 When the count value counts from 1 to reach this value, the corresponding multi-function output
terminal is activated (Pr.02-13, Pr.02-14, Pr.02-36, Pr.02-37 are set to 17). You can use this
parameter as the end of counting to make the drive run from the low speed to stop.
Desired Frequency Reached 1
Desired Frequency Reached 2
Settings
The Width of the Desired Frequency Reached 1
The Width of the Desired Frequency Reached 2
Settings
 Once output speed (frequency) reaches the desired speed (frequency), if the corresponding
multi-function output terminal is set to 3–4 (Pr.02-13, Pr.02-14, Pr.02-36, and Pr.02-37), this
multi-function output terminal is "closed".
0–65500
0–65500
0.00–599.00 Hz
0.00–599.00 Hz
12.1-02-16
Default: 0
Default: 0
Default: 60.00 / 50.00
Default: 2.00