Chapter 12 Description of Parameter SettingsCFP2000
When all the motors are running and water pressure is sufficient, the fixed time circulation is not
enabled. If motor 1 and motor 2 run to reach a balance in water pressure and when the time reaches
the setting for Pr.12-02, motor 1 runs without using mains electricity (run by the motor drive). When
the time reaches the setting for Pr.12-03, motor 3 runs using mains electricity, and the operating time
of each motor resets. Once it reaches the time setting for Pr.12-02 again, motor 2 runs without using
mains electricity. Then when time reaches the setting for Pr.12-03, motor 4 runs using mains
electricity. The time sequence Diagram 12-14 is as shown below
Diagram 12-14: Fixed Time Circulation under Fixed Amount Control Balance
Fixed Quantity Circulation Output Delay
Settings 1.0–3600.0 sec.
Under Fixed Quantity Circulation (Increment) mode, the first motor of the drive switches to the
supply mains through the setting time for Pr.12-03, then switches to the second motor through
the setting delay time for Pr.12-09.
12.1-12-16
Default: 1.0