Delta CFP2000 Series User Manual page 710

Ip55 fan and pump drive
Table of Contents

Advertisement

frequency will also be automatically sent back to the master station (D2009+n*100 and
D2013+n*100). This also illustrates how the master can handle these tasks through read/write
operations in the special D area.
Furthermore, it should be noted that the remote I/O of PDO2 can obtain the slave device's
current DI and AI status, and can also control the slave device's DO and AO status. Nevertheless,
after introducing a fully automatic mapping special D, the CFP2000 CANopen master also provides
additional information refreshes. For instance, while in speed mode, acceleration/deceleration
settings may have been refreshed. The special D therefore also stores some seldom-used
real-time information, and these commands can be refreshed using the CANFLS command. The
following is the CFP2000's current CANopen master data conversion area, which has a range of
D2001+100*n - D2033+100*n, as shown below:
1. The range of n is 0-7
2. ●Indicates PDOTX, ▲Indicates PDORX; unmarked special D can be refreshed using the
CANFLS command
Special D
Station number n of slave station
D2000+100*n
Setting range: 0–127
0: No CANopen function
D2002+100*n Manufacturer code of slave station number n (L)
D2003+100*n Manufacturer code of slave station number n (H)
Manufacturer's product code of slave station
D2004+100*n
number n (L)
Manufacturer's product code of slave station
D2005+100*n
number n (H)
Basic definitions
Special D
Communications break handling method of slave
D2006+100*n
station number n
D2007+100*n Error code of slave station number n error
D2008+100*n Control word of slave station number n
D2009+100*n Status word of slave station number n
D2010+100*n Control mode of slave station number n
D2011+100*n Actual mode of slave station number n
Velocity Control
Special D
D2001+100*n Torque restriction on slave station number n
D2012+100*n Target speed of slave station number n (rpm)
D2013+100*n Actual speed of slave station number n (rpm)
D2014+100*n Error speed of slave station number n (rpm)
D2015+100*n Acceleration time of slave station number n (ms)
D2016+100*n Deceleration time of slave station number n (ms)
Description of Function
Description of Function
Description of Function
16-137
Chapter 16 PLC Function Applications│CFP2000
PDO Default
Default
1
0
0
0
0
0
PDO Default
Default
1
0
0
0
0
2
2
PDO
Default
Default
1
0
0
0
0
1000
1000
R/W
2
RW
R
R
R
R
R/W
2
RW
R
RW
R
RW
R
R/W
2
RW
RW
R
R
RW
RW

Advertisement

Table of Contents
loading