Chapter 16 PLC Function Applications│CFP2000
Command
Action continues (ON)
SET
X0–X17
Operand
When the SET command is driven, the designated element will be set as On, and will
be maintained in an On state, regardless of whether the SET command is still driven.
The RST command can be used to set the element as Off.
Ladder diagram:
X0
Command
Clear contact or register
RST
X0–X17
Operand
When the RST command is driven, the action of the designated element will be as
follows:
Element
Y, M
T, C
D
If the RST command has not been executed, the status of the designated element will
remain unchanged.
Ladder diagram:
X0
Command
16-bit timer
TMR
Operand
When the TMR command is executed, the designated timer coil will be electrified, and
the timer will begin timing. The contact's action will be as follows when the timing
value reaches the designated set value (timing value >= set value):
N.O. (Normally Open) contact
N.C. (Normally Close) contact
If the RST command has not been executed, the status of the designated element will
remain unchanged.
Ladder diagram:
X0
Y0–Y17
Y0
SET
Y0–Y17
Both coil and contact will be set as Off.
The current timing or count value will be set as 0, and both the coil
and contact will be set as Off.
The content value will be set as 0.
Y5
RST
T-K
T0–T159, K0–K32,767
T-D
T0–T159, D0–D399
TMR
T5
Function
M0–M799
T0–159
Command code:
LD
Y1
ANI
SET
Function
M0–M799
T0–159
Mode
Command code:
LD
RST
Function
Closed
Open
Command code:
LD
K1000
TMR
16-46
C0–C79
D0–D399
Description:
X0
Load Contact a of X0
Establish parallel
Y0
connection to contact b
of Y0
Action continues (ON)
Y1
C0–C79
D0–D399
Description:
Load Contact a of X0
X0
Clear
contact
Y5
register
Description:
X0
Load Contact a of X0
T5 timer
T5 K1000
Set value as K1000
or