Delta CFP2000 Series User Manual page 266

Ip55 fan and pump drive
Table of Contents

Advertisement

01 Basic Parameters
Maximum Operation Frequency
Settings
Determines the AC motor drive's maximum operation frequency range. This setting corresponds
to the maximum value for the analog input frequency setting signal (0 – +10 V, 4–20 mA, 0–20
mA, ±10 V).
Minimum Carrier Wave Requirement
For 90 kW model, maximum operation frequency is 400 Hz (carrier should be set at least 4k)
Output Frequency of Motor 1
Output Frequency of Motor 2
Settings
 Set the value according to the motor's rated frequency from the motor's nameplate. If the motor's
rated frequency is 60 Hz, set the value to 60 Hz. If the motor's rated frequency is 50 Hz, set the
value to 50 Hz.
Output Voltage of Motor 1
Output Voltage of Motor 2
Settings
 Set the value according to the motor's rated voltage from the motor's nameplate. If the motor's
rated voltage is 220 V, set the value to 220.0 V. If the motor's rated voltage is 200 V, set the value
to 200.0 V.
 There is a wide variety of motors, but the power system for each country is different. The
convenient and economical way to solve this problem is to use an AC motor drive, which can deal
with different voltages and frequencies, while supporting the original characteristic and life of the
motor.
Mid-point Frequency 1 of Motor 1
Settings
Mid-point Voltage 1 of Motor 1
Settings
50.00–599.00 Hz
Setting range for 90 kW (125 HP): 0.00–400.00 Hz
2k
3k
4k
5k
6k
0.00–599.00 Hz
0.0–510.0 V
0.00–599.00 Hz
0.0–480.0 V
12.1-01-1
Chapter 12 Description of Parameter SettingsCFP2000
 You can set this parameter during operation.
Maximum Operation Frequency (IM VF/ IM SVC)
200 Hz
300 Hz
400 Hz
500 Hz
599 Hz
Default: 60.00 / 50.00
Default: 60.00 / 50.00
Default: 400.0
Default: 3.00
Default: 22.0