12 PUMP Parameters

Pr.
Parameter Name
12-00
Circulation Control
Number of Motors to be
12-01
connected
Operating time for each motor
12-02
(minutes)
Delay time due to the
12-03
acceleration (or the increment )
at motor switching (seconds)
Delay time due to the
12-04
deceleration ( or the decrement)
at motor switching (seconds)
Delay time due to fixed quantity
12-05
circulation at motor switching
(seconds)
Frequency when switching
12-06
motors at fixed quantity
circulation (Hz)
Action when fixed 1uantity
12-07
circulation breaks down
Frequency for stopping auxiliary
12-08
motor (Hz)
Fixed quantity circulation output
12-09
delay
Motor 1 operation record
12-10
(min./sec.)
12-11
Motor 1 operation record (hour)
Motor 2 operation record
12-12
(min./sec.)
12-13
Motor 2 operation record (hour)
Motor 3 operation record
12-14
(min./sec.)
12-15
Motor 3 operation record (hour)
Motor 4 operation record
12-16
(min./sec.)
12-17
Motor 4 operation record (hour)
Chapter 11 Summary of Parameter SettingsCFP2000
Setting Range
0: No operation
1: Fixed time circulation (by time)
2: Fixed quantity circulation
3: Fixed quantity control
4: Fixed time circulation + fixed quantity circulation
5: Fixed time circulation + fixed quantity control
1–8
0–65500 min.
0.0–3600.0 sec.
0.0–3600.0 sec.
0.0–3600.0 sec.
0.00–599.00 Hz
0: Turn off all output
1: Motors powered by mains electricity continues to
operate
0.00–599.00 Hz
1.0–3600.0 sec.
Read only
Read only
Read only
Read only
Read only
Read only
Read only
Read only
11-37
Default
0
1
0
1.0
1.0
10.0
60.0
0
0.00
1.0
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only
Read
only