Delta CFP2000 Series User Manual page 283

Ip55 fan and pump drive
Table of Contents

Advertisement

Chapter 12 Description of Parameter SettingsCFP2000
Settings
Functions
23
Input the counter value
24
FWD JOG command
25
REV JOG command
28
Emergency stop (EF1)
Signal confirmation for
29
Y-connection
Signal confirmation for
30
-connection
Disable EEPROM write
38
function (parameters
memory disable)
40
Force coasting to stop
41
HAND switch
42
AUTO switch
ON: the counter value increases by 1. Use the function with
Pr.02-19.
This function is valid when the source of the operation command is
external terminal. ON: the drive executes forward JOG.
This function is valid when the source of the operation command is
external terminal. ON: the drive executes reverse JOG.
ON: the output of the drive stops immediately, displays EF1 on the
keypad, and the motor is in the free run status. The drive keeps
running until the fault is cleared after you press RESET on the
keypad (EF: External Fault).
When the control mode is V/F, ON: the drive operates by the first
V/F.
When the control mode is V/F, ON: the drive operates by the
second V/F.
ON: writing to EEPROM is disabled. Changed parameters are not
saved after power off
ON: during operation, the drive free runs to stop.
1.
When the MI terminal switches to OFF, it executes a STOP
command. Therefore, if the MI terminal switches to OFF
during operation, the drive stops.
2.
Use the keypad KPC-CC01 to switch between HAND and
AUTO. The drive stops first, and then switches to HAND or
AUTO status.
3.
The digital keypad KPC-CC01 displays the current status of
the drive (HAND/OFF/AUTO).
OFF
AUTO
HAND
OFF
12.1-02-6
Descriptions
bit1
bit0
0
0
0
1
1
0
1
1

Advertisement

Table of Contents
loading

Table of Contents