Delta CFP2000 Series User Manual page 392

Ip55 fan and pump drive
Table of Contents

Advertisement

3. PID Feedback Rate Percentage ( Use PID, Pr.08-00 ≠ 0 and Pr.08-18=1)
When the PID feedback rate reaches the sleep level percentage, the drive starts to count the
sleep time. The output frequency also decreases. If the drive exceeds the preset sleep time, it
goes to sleep mode (0 Hz). If the drive does not reach the sleep time, it remains at the lower limit
(if there is a preset of lower limit.), or it remains at the lowest output frequency set for Pr.01-07 and
waits to reach the sleep time before going into sleep mode (0 Hz).
When the PID feedback value reaches the wake-up percentage, the drive starts to count the
wake-up delay time. Once it reaches the wake-up delay time, the drive starts the acceleration time
to reach the PID frequency command value.
Example 01: PID negative feedback
Pr.08-10 must > Pr.08-11
30 kg is the reference
Set the parameter:
Pr.03-00=5 (AVI1 is PID feedback)
Pr.08-00=1 (PID negative feedback: AVI1
Pr.08-10=40% (Sleep reference:
Pr.08-11=20% (Wake-up reference:
Case 01: If feedback >12kg, frequency decrease.
Case 02: If feedback < 6kg, frequency increase.
simulation input function select)
12 kg = 40%*30 kg)
6 kg = 20% * 30 kg)
Chapter 12 Description of Parameter SettingsCFP2000
Sleep area
Excessive
Wake-up
12.1-08-11
PID
Area
Physical quantity
>12 kg, the drive goes
into sleep, the motor
goes into sleep
between 6 kg and 12
kg, the drive remains in
area
current state
< 6 kg, the drive
wakes-up, the motor
area
wakes-up